Diesel Generator Fuel Consumption Chart (Litres per Hour)
Planning how much diesel your generator needs is the first step to avoiding a shutdown, and to budgeting fuel properly. This chart shows the approximate diesel consumption of generators in litres per hour, by generator size and load, with worked examples for typical sites in Dubai and the Northern Emirates.
Diesel generator fuel consumption chart (litres per hour)
| Generator size (kW) | Approx. kVA | 1/4 load (L/hr) | 1/2 load (L/hr) | 3/4 load (L/hr) | Full load (L/hr) |
|---|---|---|---|---|---|
| 20 | 25 | 2.3 | 3.4 | 4.9 | 6.1 |
| 30 | 38 | 4.9 | 6.8 | 9.1 | 11.0 |
| 40 | 50 | 6.1 | 8.7 | 12.1 | 15.1 |
| 60 | 75 | 6.8 | 11.0 | 14.4 | 18.2 |
| 75 | 94 | 9.1 | 12.9 | 17.4 | 23.1 |
| 100 | 125 | 9.8 | 15.5 | 22.0 | 28.0 |
| 125 | 156 | 11.7 | 18.9 | 26.9 | 34.4 |
| 150 | 188 | 13.6 | 22.3 | 31.8 | 41.3 |
| 200 | 250 | 17.8 | 29.1 | 41.6 | 54.5 |
| 250 | 313 | 21.6 | 36.0 | 51.5 | 68.1 |
| 300 | 375 | 25.7 | 42.8 | 60.9 | 81.4 |
| 400 | 500 | 33.7 | 56.4 | 80.6 | 108.3 |
| 500 | 625 | 41.6 | 70.0 | 99.9 | 135.1 |
| 600 | 750 | 50.0 | 83.3 | 119.2 | 162.0 |
| 750 | 938 | 61.7 | 103.7 | 148.8 | 202.1 |
| 1000 | 1250 | 81.8 | 137.8 | 197.2 | 269.1 |
These are industry-standard estimates for a typical diesel generator. Real consumption varies with the engine make, age, maintenance, ambient temperature and how steady the load is. Always check your generator’s own data sheet.
How to read the chart
- Find your generator size in kW. If your generator is rated in kVA, multiply by 0.8 (the usual power factor). A 500 kVA set is about 400 kW.
- Estimate your normal load. Most generators run between 50% and 75% of their rating. Standby sets that only run during outages often run lower.
- Multiply by your running hours. Litres per hour × hours per day gives daily consumption, and × days gives your monthly diesel requirement.
Worked examples
Construction site: 500 kVA generator at 75% load, 24 hours a day
500 kVA ≈ 400 kW. At 3/4 load the chart gives about 80.6 L/hr. Over 24 hours that is roughly 1,935 litres per day, or about 58,000 litres per month. At this level, scheduled bulk delivery every one to two days is usually the most practical option.
Building standby generator: 250 kVA at 50% load, 10 hours of use per month
250 kVA ≈ 200 kW. At half load the chart gives about 29.1 L/hr, so 10 hours of testing and outages uses roughly 290 litres per month. The priority here is keeping the tank full so the generator is ready when the grid fails.
Event or temporary site: 100 kVA at 50% load, 12 hours a day for 5 days
100 kVA ≈ 80 kW, which uses roughly 12–15 L/hr at half load. Over 60 hours that is about 800–900 litres.
Estimating your diesel cost
Multiply your monthly litres by the diesel price. UAE diesel prices change every month; see the official UAE diesel price for this month. Bulk prices for businesses depend on volume, location and delivery schedule, so ask for a quote based on your actual consumption.
Tips to keep generators running and fuel costs down
- Don’t let tanks run low. Schedule top-ups when the tank reaches about 30–40%, especially for 24-hour sites.
- Size the generator to the load. A generator running at very light load wastes fuel and can suffer wet stacking. Running in the 50–80% range is usually most efficient.
- Use clean, low-sulphur diesel. Contaminated fuel blocks filters and injectors. Buy from an authorized supplier and keep tanks clean.
- Track consumption. Compare delivered litres with running hours every month; a sudden jump can point to leaks, theft or an engine problem.
- Maintain the engine. Regular servicing, clean air filters and correct injector settings keep consumption close to the chart.
Frequently asked questions
How much diesel does a 100 kVA generator use per hour?
A 100 kVA generator is about 80 kW. At half load it uses roughly 12–15 litres of diesel per hour, and around 24 litres per hour at full load. Actual use depends on the engine, its age and maintenance, and the load.
How much diesel does a 500 kVA generator use per day?
A 500 kVA generator is about 400 kW. At 75% load it uses roughly 80 litres per hour, or about 1,900–2,000 litres over 24 hours.
How do I convert kVA to kW for a generator?
Most diesel generators are rated at a power factor of 0.8, so kW ≈ kVA × 0.8. For example, 250 kVA ≈ 200 kW.
How often should a generator tank be refilled?
Divide the usable tank capacity by the hourly consumption at your normal load. Many sites schedule bulk diesel top-ups when the tank reaches about 30–40% so there is always a safety margin.
Generator diesel delivery in Dubai and the Northern Emirates
Barrel Energy L.L.C., an authorized ENOC / EPPCO diesel dealer since 2007, refills standby and prime-power generators for buildings, construction sites, hotels, events and facilities across Dubai, Sharjah, Ajman, Umm Al Quwain, Ras Al Khaimah and Fujairah, on a schedule or in an emergency. See our diesel supply services, call +971 4 268 0404, use our 24-hour hotline +971 50 654 7905, or message us on WhatsApp.